Classic I, Division 2 Solutions/Data Acquisition Modules

ADVANTECH ADAM-4012-DE

Why buy from GID?

Quality

We are industry veterans who take pride in our work

Protection

Avoid the dangers of risky trading in the gray market

Access

Our network of suppliers is ready and at your disposal

Savings

Maintain legacy systems to prevent costly downtime

Speed

Time is of the essence, and we are respectful of yours

Details

Part Number ADAM-4012-DE
Manufacturer ADVANTECH
Category Classic I, Division 2 Solutions »  Data Acquisition Modules
Price Request Quote
Lead Time Request Quote

Description

Analog input modules use a microprocessor-controlled integrating A/D converter to convert sensor voltage, or current signals into digital data. The digital data is then translated into either engineering units, twos complement hexadecimal format or percentage of full-scale range (FSR)according to the module 's configuration. When prompted by the host computer, the data is sent through a standard RS-485 interface. The Analog Input Modules offer signal conditioning, A/D conversion, ranging, and RS-485 digital communication functions. They protect your equipment from ground loops and power surges by providing opto-isolation of the A/D input and transformer based isolation up to 3000 V DC.

Request a Quote

* indicates a required field.
Your Contact Information
Your Company/Organization
Your Requirement
By sending us your information, you are affirming your agreement with our Privacy Policy.
You will not receive unsolicited communications.

Our Process

Our Process: Preparation
Preparation

Once you accept your quote and confirm your order, we prepare by retrieving related parts and components from our inventory. Anything we do not currently have in stock is sourced.

Our Process: Receiving
Receiving

Upon receipt, all parts are visually inspected for damage and then photographed to document their condition. Parts acquired from vendors must meet our quality standards.

Our Process: Initial Testing
Initial Testing

Industrial computer boards and other parts we are equipped to evaluate are tested to verify functionality and discover possible damage.

Our Process: Refurbishment
Refurbishment

Industrial computer boards have all components with low MTBF numbers (such as capacitors and connectors) replaced and are washed in our PCB cleaner to remove dust and grime.

Our Process: Repair
Repair

Industrial computer boards are fully diagnosed and repaired by our engineers. Logs of the problems encountered and solutions implemented are recorded.

Our Process: Final Testing
Final Testing

Industrial computer boards have all I/O connections rigorously tested to ensure that everything is working properly before the board is certified as ready to ship.

Our Process: Shipping
Shipping

After photos are taken to document the exterior condition of the part, it is packaged and sent to the customer. ESD-safe materials are used to protect sensitive equipment on its journey.

Who We Are

IPC Station is a website of GID Industrial, an ISO 9001:2015-certified company that has specialized in servicing industrial computer boards and providing other industrial products for sectors including manufacturing, defense, aerospace, entertainment, healthcare, and more by utilizing our combined skills and vast international network of trusted suppliers since our founding in 2015.

Do you need an ADAM-4012-DE? We can help you find it at a competitive price!

Specifications

Display LED Indicators Power
Power Supply Power Requirement 10~30 VDC
Analog Input Channels 1 differential
Analog Input Voltage Range ±150 mV ±500 mV ±1 V ±5 V ±10 V
Analog Input Current Input ±20 mA
Analog Input Sampling Rates 10 samples/second
Analog Input Resolution 16-bit
Analog Input Input Impedance Voltage: 20 MOhm Current: 125 Ohm
Analog Input Span Drift ±25 ppm/°C
Analog Input Zero Drift ±6 µV/°C
Analog Input CMR @ 50/60 Hz 150 dB
Analog Input NMR @ 50/60 Hz 100 dB
General Watchdog Timer System (1.6 second)
General Connector 1 x plug-in terminal block (#14~22 AWG)
General Temperature (Operating) -10~70 °C (14~158 °F)
General Humidity 5~95 %RH
General Temperature (Storage) -25~85 °C (-13~185 °F)
General Interface RS-485
General Isolation Protection 3000 VDC
General Communication Protocol ASCII command
General Communication Speed Serial: From 1,200 to 115.2 k
General Comm. Distance Serial: 1.2 km
General Data Flow Control Yes
Digital Input Channles 1
Digital Input Input Voltage Logic level 0: 1 V max. Logic level 1: 3.5~30 V
Digital Output Channels 2 Open collector to 30V, 30 mA max. load
Digital Output Power Dissipation 300 mW
Categorization Information Industrial Automation
Class I, Division 2 Solution
Data Acquisition Modules

Datasheet

Download "cab48bd4-443d-4071-9221-12b985762dd2.pdf" (269 KiB)

Extracted Text

1-ch Analog Input Module ADAM-4012 ADAM-4013 1-ch RTD Input Module ADAM-4015 6-ch RTD Module with Modbus RoHS RoHS RoHS ADAM-4012 ADAM-4013 COMPLIANT COMPLIANT ADAM-4015 COMPLIANT 2002/95/EC 2002/95/EC 2002/95/EC Specifications Specifications Specifications General General General ƒ Power Consumption 1.2 W @ 24 V ƒ Power Consumption 0.7 W @ 24 V ƒ Connectors 2 x plug-in terminal blocks DC DC (#14 ~ 28 AWG) ƒ Supported Protocols ASCII command ƒ Supported Protocols ASCII command ƒ Power Consumption 1.2 W @ 24 V DC ƒ Connectors 1 x plug-in terminal block ƒ Connectors 1 x plug-in terminal block ƒ Watchdog Timer System (1.6 s) & (#14 ~ 22 AWG) (#14 ~ 22 AWG) Communication ƒ Supported Protocols ASCII command and Analog Input Analog Input Modbus/RTU ƒ Channels 1 ƒ Burn-out Detection Yes ƒ Channels 1 ƒ Input Impedance Voltage: 20 MΩ ƒ Input Connections 2 or 3-wire Analog Input Current: 125 Ω (Added ƒ Input Impedance 2 MΩ by user) ƒ Channels 6 differential ƒ Input Type Pt or Ni RTD ƒ Input Connections 2, 3-wire ƒ Input Type mV, V or mA ƒ RTD Types and Temperature Ranges ƒ Input Impedance 10 MΩ ƒ Input Range ±150 mV, ±500 mV, ±1 V, ƒ Input Type Pt, Balco and Ni RTD IEC RTD 100 ohms ±5 V, ±10 V and ±20 mA ƒ RTD Types and Temperature Ranges Pt -100°C to +100°C a = 0.00385 ƒ Accuracy Voltage mode: ±0.1% or Pt 100 RTD: Pt 0°C to +100°C a = 0.00385 better Pt -50°C to 150°C Pt 0°C to +200°C a = 0.00385 Current mode: ±0.2% or Pt 0°C to 100°C Pt 0°C to +600°C a = 0.00385 better Pt 0°C to 200°C JIS RTD 100 ohms Pt 0°C to 400°C ƒ Span Drift ±25 ppm/°C Pt -100°C to +100°C a = 0.003916 Pt -200°C to 200°C ƒ Zero Drift ±6 µV/°C Pt 0°C to +100°C a = 0.003916 IEC RTD 100 ohms (a = 0.00385) Pt 0°C to +200°C a = 0.003916 JIS RTD 100 ohms (a = 0.00392) Digital Input Pt 0°C to +600°C a = 0.003916 Pt 1000 RTD ƒ Channels 1 Pt -40°C to 160°C Ni RTD Logic level 0: 1 V max. Balco 500 RTD Ni -80°C to +100°C Logic level 1: 3.5 ~ 30 V -30°C to 120°C Ni 0°C to +100°C pull up current: 0.5 mA, Ni 50 RTD ƒ Accuracy ±0.1% or better 10 kΩ resistor to 5 V Ni -80°C to 100°C ƒ Span Drift ±25 ppm/°C Ni 508 RTD ƒ Event Counter Max. input freq.: 50 Hz Ni 0°C to 100°C Min. input pulse width: 1 ƒ Zero Drift ±3 µV/°C BA1 msec. ƒ CMR @ 50/60 Hz 150 dB -200°C to 600°C ƒ Accuracy ±0.1% (Typical) Digital Output ƒ CMR @ 50/60 Hz 120 dB ƒ Channels 2, open collector to 30 V, ƒ Span Drift ± 25 ppm/°C 30 mA max. load ƒ Zero Drift ± 3 µV/°C ƒ Power Dissipation 300 mW Common Specifications Ordering Information ƒ ADAM-4012 1-ch Analog Input ƒ NMR @ 50/60 Hz 100 dB General Module ƒ Isolation Voltage 3,000 V DC ƒ Power Input Unregulated 10 ~ 30 V DC ƒ ADAM-4013 1-ch RTD Input Module ƒ Connectors 1 x plug-in terminal block Environment ƒ ADAM-4015 6-ch RTD Module with (#14 ~ 22 AWG) ƒ Operating Humidity 5 ~ 95% RH Modbus ƒ Watchdog Timer System (1.6 second) ƒ Operating -10 ~ 70°C (14 ~ 158°F) Analog Input Temperature ƒ Storage Temperature -25 ~ 85°C (-13 ~ 185°F) ƒ Resolution 16-bit ƒ Sampling Rate 10 sample/second (total) RS-485 I/O Modules: ADAM-4000 All product specifications are subject to change without notice Last updated : 27-Jul-2016

Related Products

ADVANTECH
Analog input modules use a microprocessor-controlled integrating A/D conver...
ADVANTECH
ADAM-4080/4080D Counter/frequency input module has two 32-bit counter input...
ADVANTECH
Robust 8-ch Thermocouple Input Module with Modbus
ADVANTECH
Robust 15-ch Digital I/O Module with Modbus
ADVANTECH
The ADAM-4510 repeaters simply amplify, or boost, existing RS-485 signals t...
ADVANTECH
Fiber optic transmission offers the benefits of wide bandwidth, immunity to...

Disclaimer

Any product names, logos, brands, and other trademarks or media featured or referred to on IPC Station are the property of their respective owners.

GID Industrial is not an authorized distributor, reseller, or representative for the products featured on this site, and is not affiliated with, sponsored by, or endorsed by any of the manufacturers or holders of the rights to the aforementioned products.

All information on this site is displayed strictly for identification purposes and does not indicate a relationship with or an approval from any third parties.

IPC Station is a GID Industrial website.
GID Industrial Logo
Copyright © 2024 GID Holdings LLC, All Rights Reserved.
Page generated in 0.419 seconds.